` 1. The architectural drawings for a G+7 residential building in zone 5 has been provided. The floor plan is the same for all 7 floor levels. Possible column positions have also been provided. Conceptualize a framing plan layout and then model the building in Etabs. The following architectural drawings have been provided:…
Sandeep Ghosh
updated on 06 Oct 2022
`
1. The architectural drawings for a G+7 residential building in zone 5 has been provided. The floor plan is the same for all 7 floor levels. Possible column positions have also been provided. Conceptualize a framing plan layout and then model the building in Etabs. The following architectural drawings have been provided:
The structural model must comply with provisions of IS 1893 and IS 13920.
Run a modal response spectrum analysis and check analysis results of the etabs model for inter-storey drift requirements, vertical & planar irregularities, minimum shear wall requirements,maximum axial load ratio for column and shear walls, effective moment of inertia for beams and columns etc
AIM:- To model and analyse the architectural plan for a G+7 residential building in zone 5. To run a model response spectrum analysis and to check the analysis results of the etabs model for inter-storey drift requirements, vertical and planar requirements, minimum shear wall requirements etc.
INTRODUCTION:- All the steps are going to be mentioned along with step by step procedure.
PROCEDURE:-
a
a) Dead load and live load Calculations:-
1. Live loads imposed for different occupancies as per clause 3.1, 3.3.1 and 4.1.1 IS 875 (Part 2) - 1987
2. Live load for slabs as per architectural drawing:-
Bedrooms:- 2 KN/m^2
Balcony:- 3 KN/m^2
Kitchen:- 3 KN/m^2
Toilet:- 2 KN/m^2
Drawing Room:- 4 KN/m^2
Corridor, passage, staircase:- 3 KN/m^2
3. Apply live load for bedroom 2 KN/m^2, balcony 3 KN/m^2, Kitchen 3 Kn/m^2, Toilet 2 KN/m^2, drawing room 4 KN/m^2 , corridor passage and staircase 3KN/m^2 as per floor plan to the ETABS model
4. Live load for roof load provided in IS 875 (Part 2)- 1987 clause 4.1
5. Apply roof load 1.5 KN/m^2 to the ETABS model
6. Calculation of dead load in slabs:-
1) Floor finish
Weight of ceiling plastering = Thickness* Unit weight = 0.015*21 = 0.315 KN/m^2
Weight of cement mortar = Thickness * Unit Weight = 0.025*21 = 0.525 KN/m^2
Weight of tiles = Thickness * Unit weight of tiles = 0.025*23 = 0.575 KN/m^2
Total weight of floor finish = 0.315+0.525+0.575 = 1.415 KN/m^2 which is approx equal to 1.5 KN/m^2
2) Roof finish
Ceiling plastering = 0.015*21 = 0.315 KN/m^2
Weathering Coarse = 0.075*23 = 1.725 KN/m^2
Cement flooring = 0.025*21 = 0.525 KN/m^2
Total weight of roof finish = 0.315+1.725+0.525 = 2.5 KN/m^2
7. Apply dead load of floor finish 1.5 KN/m^2 and roof finish of 2.5 KN/m^2 to the ETABS model.
8. Calculation of brick wall load
Weight of outer wall load = Unit weight of AAC bricks*Thickness*Height of wall + Unit weight*Thickness* Height of wall = 6*0.3*(3-0.45)+20*0.024*2.55 = 5.8 KN/m
Weight of inner wall load = Unit weight of AAC bricks*Thickness*Height of wall + Unit weight*Thickness*Height of wall = 6*0.15*(3-0.45)+0.024*2.55*20 = 3.5 KN/m
9. Apply outer wall load of 5.8 KN/m and 3.5 KN/m to the ETABS model
9. Calculation of parapet load
Consider height of wall = 1.2 m
Weight of parapet wall = 1.2*0.15*6+0.024*1.2*20 = 1.656 KN/m
10. Apply parapet load of 1.656 KN/m to the main beam in ETABS model
11. Calculation of mumty wall load for roof ( Along grid line A-4 to B-4 and A-3 to A-3 to B-3)
Weight of mumty load = (2.5-0.45)*0.3*6+0.024*(2.5-0.45)*20 = 4.674 KN/m
12. Apply mumty wall load of 4.674 KN/m to the main beam in ETABS model
13. Calculation of water tank
Given data: Water tank = 20 KL =20000 L = 20 m^3
Mass of water = Volume*Density = 20*10.25 = 205 KN
Consider length of tank = 5 m
Width of tank = 2.5 m
Area of water tank = 5*2.5 = 12.5 m^2
Height of tank = Volume/Area = 20/12.5 = 1.6 m
Dead load per unit area = 205/12.5 = 16.4 KN/m^2
Weight of mortar, water proofing etc = 4 KN/m^2
Toad dead load on base slab = 16.4+4 = 20.4 KN/m^2
Live load on base slab as per IS 875 (Part 2-1987) = 0,75 KN/m^2
Thickness of overhead water tank = 300 mm = 0.3 m
Dead load on beam = (20.4+0.75)*0.3*2 = 12.69 KN/m
14. Apply dead load of 20.4 KN/m^2 to the base slab in ETABS model
Apply live load of 0.75 KN/m^2 to the base slab in ETABS model
Apply load of 12.69 KN/m to the main beam in ETABS model
b) Earthquake load calculations
1. Calculation of time period along X direction:-
Height of the building = 25 m
Dimension of the building along x direction = 19.75 m
Time period, t = 0.09*h/√√d = 0.09*25/√19.75 = 0.506 s
2. Calculation of time period along Y direction:-
Height of the building = 25 m
Dimension of the building along y direction = 19.8 m
Time period, t = 0.09*h/√d = 0.09*25/√19.8 = 0.506 s
3. Apply time period of 0.506 s to the ETABS model
c) Live load reduction factors
Live load has been reduced on floor as per clasue 3.2.1 on IS 875 (Part 2)- 1987
d) Load combinations
Go to define > load combinations
e) Model case
Click on load case
Click on modal/ show case
Maximum number of modes are to be chosen as 20
f) Mass source
Percentage of imposed loads to be considered in calculation of seismic weight is given as per clause 7.3.1 (IS 1893 Part 1 -2016)
Define mass source
Click on modify mass source
Calculate percentage of dead load, brick wall and floor finishes as 100 percentage and live load as 25 percentage
Select shell diaghram for in-plane flexibility
g) Respone spectrum functions
Go to define> functions> Response spectrum
After assigning go to define load cases
Add load case name as Rsx and Rsy for response spectrum functions in x and y axis directions respectively
h) Run Analysis
Check the model
Mobel has been checked. No error messages
Run the analyis
i) Output Data
A. Base shear reactions and response reduction reactions
Since the linear static method and response reduction factor for base shear reactions are not same then we have to separate multiply the factors as per clause 7.7.3 (IS 1893 Part 1 - 2016)
Therefore divide (3315.0315/2503.9119) = 1.32*36402.28 (Scale factor) = 48051 in x axis
(3315.0315/3358.0155) = 0.98*43678.81 = 42805.23 in y axis
Reanalyse it and check the model
Base shear reactions in x axis for linstatic = 3484.2393 KN
Base shear reactions in y axis for linstatic = 3484.2392 KN
Base shear reactions in x axis for Response spectrum analysis = 3509.2749 KN
Base shear reaction in y axis for Response spectrum analysis = 3571.3194 KN
B. Model Participation mass ratios
Model partcipation for first mode = 66% which is in z direction
Model participation for second mode = 75.93 % which is in y direction
Model participation for third mode = 74.69 % which is in x axis
First and second modes atleast differ by 10 percent
C. Inter story drift limitations
D. Minimum shear wall requirements
Total base shear reactions for individual shear wall in x axis = 2953.58 KN
Total base shear reactions in x axis = 3463.82 KN
Percentage of base shear reactions to be carried out = (2953.78/3463.82)*100 = 85.27% > 80% which is OK
Total base shear reactions for individual shear wall in y axis = 2390.85 Kn
Total base shear reactions in y axis = 3487.57 KN
Leave a comment
Thanks for choosing to leave a comment. Please keep in mind that all the comments are moderated as per our comment policy, and your email will not be published for privacy reasons. Please leave a personal & meaningful conversation.
Other comments...
Week 1 Challenge
1. 1. Write the steps involved to upload a .std file through web mail? 2. Name the different materials that can be designed using STAAD Pro. 3. Is it possible to capture images in STAAD Pro? If yes how? 4. Name the three ways by which you can create a model. 5. Write…
19 Dec 2022 05:41 PM IST
Foundation Design using SAFE
1.Model the isolated footing provided in week 11 challenge on SAFE. Analyze and design it to verify the size, depth and steel provided as per calculations. AIM:- To model the isolated footing by using SAFE and to analyze and to design it to verify the size, depth and calculation of steel provided INTRODUCTION:-…
14 Oct 2022 03:42 AM IST
Design of Shallow Foundation (Isolated Footings)
1. Design a square footing for a column size of 400x400. The compression axial load for the load combination of (1.5 DL + 1.5 LL) is 2000 KN. The safe soil bearing capacity is 150 KN/m2 at a depth of 2 meters below E.G.L. Participants are free to go for either a tapered or stepped footing. Besides the total axial load,…
08 Oct 2022 06:08 PM IST
Structural Modelling using Etabs 2018
` 1. The architectural drawings for a G+7 residential building in zone 5 has been provided. The floor plan is the same for all 7 floor levels. Possible column positions have also been provided. Conceptualize a framing plan layout and then model the building in Etabs. The following architectural drawings have been provided:…
06 Oct 2022 11:13 AM IST